Every calculator here publishes what it assumes. This page collects the models, the constants,
and — more importantly — where each one stops being accurate. If a number cannot be defended,
it does not belong on this site.
Cable voltage drop
ρ(T) = ρ₂₀ × [1 + α × (T − 20)]
R = ρ(T) × L ÷ (A × n)
ΔV_dc = I × 2R ΔV_1φ = I × 2R × cos φ ΔV_3φ = √3 × I × R × cos φ
- ρ₂₀: copper 17.241 Ω·mm²/km, aluminium 28.264 Ω·mm²/km (IACS, 100 % annealed).
- α: copper 0.00393 /°C, aluminium 0.00403 /°C.
- Reactive drop (inductance) is neglected: the tool is resistive-only. Below roughly
25 mm² that is immaterial; above 95 mm² at poor power factor the true drop is a few
percent worse — run a reactance-inclusive tool before finalising large feeders.
- Standard sizes: IEC 60228 metric series and AWG/kcmil equivalents.
Not covered: ampacity (IEC 60364-5-52 / NEC Table 310.16 depend on installation method,
grouping, ambient), short-circuit withstand, protective coordination.
Voltage rise from an exporting inverter
I_export = P ÷ (V × phases)
ΔV_rise = I_export × 2R (1φ) ΔV_rise = √3 × I_export × R × cos φ (3φ)
- Identical to the drop formula; only the sign of the current changes. The drop result on
the voltage drop page can be read directly as a rise.
- R is the impedance from the transformer to the point of connection, not the whole feeder.
- The tool does not model the upstream network impedance or the transformer's tap position,
so it gives the rise contributed by your cable only. The grid's pre-existing voltage —
which is at its daily maximum when every system on the feeder is exporting — adds on top.
- The acceptable limit (commonly around 1–2 % at the point of connection) comes from the
grid connection agreement. It is a contractual number and varies by network; no calculator
can supply it.
Solar string configurator
V_oc(T) = V_oc,STC × [1 + α_voc × (T − 25)]
N_s,max = floor( V_dc,max × (1 − margin) ÷ V_oc(T_min) )
N_s,min = ceil( V_mppt,low ÷ V_mp(T_max) )
- α_voc from the module datasheet, typically −0.25 to −0.30 %/°C for crystalline silicon.
- The margin on the cold-morning ceiling (default 3 %) covers the irradiance-driven
low-temperature edge case and inverter tolerance.
- Records cold-record temperature and hot-cell temperature as separate inputs; using the
same number for both is the classic string-sizing error.
Battery bank sizer
C_eol = E_load × N ÷ (η_inv × √η_rte × DoD × f_T × SOH_EOL)
- Round-trip efficiency split as √η_rte per direction; charge-side losses are already
paid upstream by the PV array.
- Temperature factors f_T: lithium interpolated from −20/−10/0/10/25 °C test points
(0.60/0.80/0.90/0.97/1.00 for LFP); lead-acid similar but with a slight high-temperature bonus.
- C-rate limits used for the check: LFP 1 C, NMC 1.5 C, AGM 0.2 C, OPzV 0.1 C — storage
duty, continuous. Match against the specific BMS and datasheet.
- Peukert effects on lead-acid are not modelled explicitly; the conservative C-rate
limit is the proxy.
PV energy yield
GTI = GHI × TF(tilt, lat) × AF(azimuth)
PR = [1 + γ(T_cell − 25)] × η_inv × (1−s)(1−m)(1−dc)(1−ac) × A
E₁ = kWp × GTI × PR × (1 − clip)
- Transposition: isotropic-sky model (Liu–Jordan) with 0.2 ground albedo, tabulated on a
latitude × tilt grid and bilinearly interpolated. Accuracy ±5 % vs hourly models for
equator-facing fixed tilt.
- Azimuth factor: empirical mid-latitude curve, 1.00 at 0° to 0.74 at ±90°.
- Cell temperature: T_cell = T_amb + 6 + GHI/280 + 0.8 × max(0, T_amb − 20) — an annual
irradiance-weighted shortcut that stays within ~1 % of hourly NOCT models at mid latitudes.
- Clipping: leave the yield tool at 0 % and run the
inverter sizing calculator, which derives the clipping loss
from your site conditions rather than assuming a generic curve.
- Overall band: expect ±8–10 % vs PVGIS/PVSyst. This is a screening tool; it is not
bankable-grade and does not model shading, horizon, or snow.
Inverter sizing & DC/AC ratio
T_cell = T_amb + (NOCT − 20) ÷ 800 × G
k = (G ÷ 1000) × [1 + γ × (T_cell − 25)]
R_th = 1 ÷ (k × η_inv) ← clipping begins above this DC/AC
loss_clear-sky day = (1 − x_th)^1.5, x_th = R_th ÷ R_actual
loss_annual = f_clear × loss_clear-sky day
- Cell temperature uses the standard NOCT form with irradiance in W/m²; γ is the datasheet
Pmax coefficient (typically −0.35 to −0.45 %/°C for crystalline silicon).
- The clipping term is derived, not fitted. Modelling the clear-sky day as
G(t) = G_peak(1 − t²) gives a time-above-irradiance of
H_day × √(1 − G/G_peak); integrating the energy above the inverter ceiling
over that profile reduces to (1 − x_th)^1.5. It was checked against numerical
integration at six thresholds and matches to within 1 × 10⁻⁴.
f_clear — the share of annual energy produced under near-clear skies — is an
input (default 55 %): 50–60 % temperate, 65–75 % desert, lower in humid equatorial and
maritime climates. It is the dominant source of uncertainty: treat the annual loss as
±30 % in relative terms.
- Indicative output on a temperate site (33 kWp, 30 °C peak ambient, NOCT 45, γ −0.35):
0 % at DC/AC 1.17 and below, 0.2 % at 1.20, 1.7 % at 1.30, 3.6 % at 1.40, 7.5 % at 1.60.
- Inverter efficiency is a single weighted constant. Real part-load sag is not modelled, so
a badly oversized inverter performs slightly worse than the tool reports.
Not covered: DC input current and MPPT allocation (see the string configurator),
conductor ampacity, overcurrent protection, DC isolator ratings, grid-code compliance.
Short-circuit current
The transformer impedance percentage is a per-unit figure, so it becomes ohms through the base
impedance Z_base = V² ÷ S and is split into resistance and reactance with the
X/R ratio. The cable adds its own resistance (from IACS conductivity, corrected to conductor
temperature) and reactance (supplied by you, 0.08 Ω/km being a fair LV default). The two are
added as complex numbers and the fault current follows from Ohm's law on the magnitude.
Isc = V_LL ÷ (√3 × |Z_tx + Z_cable|)
Isc,LN = (V_LL ÷ √3) ÷ |Z_tx + Z_phase + Z_neutral|
- The peak factor
κ = 1.02 + 0.98·e^(−3 R/X) is the IEC 60909-0 expression. It is
used here for its arithmetic: at high X/R the DC offset decays slowly and the first peak
approaches twice the RMS crest; at low X/R it decays fast and κ falls towards 1.02. Busbar
bracing and contact-welding ratings are quoted against this peak, not the RMS value.
- The result is a floor, not a ceiling. Only the transformer positive-sequence
impedance and one cable are modelled. Utility source impedance, motor contribution, parallel
transformers and generators all raise the real fault current.
- The line-to-neutral figure uses the positive-sequence impedance for the return path too.
True zero-sequence impedance differs — more so with a reduced neutral or a delta-wye
transformer — so the direction of the error depends on the earthing arrangement.
- Cable reactance is a single input. Spacing, armouring and conductor shape move it, and on
long runs it can matter more than resistance.
Not covered: protective device selection, breaking capacity, discrimination,
disconnection time, and the k factor for thermal withstand — those belong to the applicable
code. The adiabatic minimum shown on the page is informational only.
Solar row spacing
Sun position comes from the standard low-precision solar equations: declination from the day of
year, hour angle from solar time, then altitude and azimuth from spherical trigonometry. The
declination expression δ = −23.44°·cos(360/365·(N+10)) is accurate to roughly half
a degree across the year, which is far tighter than the shadow geometry needs.
sin α = sin φ · sin δ + cos φ · cos δ · cos h
D = H · cos(A − A_array) ÷ tan α
GCR = w · sin(tilt) ÷ (w · cos(tilt) + D)
- The
cos(A − A_array) term is the one most spreadsheets omit. A shadow
points directly away from the sun, so only the component along the row-pitch axis reaches the
next row. Early in the morning the sun sits well off the side of a south-facing array and the
shadow falls diagonally, contributing less than its full length. Skipping this over-states the
required gap.
- When the sun is abeam of the array (90° off the azimuth) the projection is zero: no amount
of that shadow touches the next row. Behind the array it is also zero.
- Solar time is not clock time. Longitude within the time zone, daylight saving and the
equation of time together can shift the two by more than an hour, which is enough to
under-size every row on a site.
- Flat ground and a uniform obstruction height are assumed. Sloping sites break both
assumptions: a north-facing slope is worse than the model says, a south-facing one better.
Not covered: single-axis trackers (their obstruction height and effective width change
continuously, and backtracking changes the optimum again), terrain or building horizons, and any
setback or fire-access requirement from local code — those usually dominate row pitch anyway.
Earthing and grounding resistance
R₁ = ρ ÷ (2πL) × [ ln(8L/d) − 1 ]
Rₙ = (R₁ ÷ n) × (1 + λα), α = ρ ÷ (2πsR₁), λ = 2H(n−1) − 2(n−1)/n
R_ring = ρ ÷ (2π²a) × [ ln(8a/r) + ln(1 + h/2a) − 1.116 ]
R_g = ρ × [ 1/L_T + 1/√(20A) × (1 + 1/(1 + h√(20/A))) ]
- Sources: rod formula from Dwight (1936), tabulated in IEEE Std 142 Table 13, BS 7430 and
IEEE Std 80. Group coupling λ reproduces the values BS 7430 tabulates — 1.000 for two rods,
3.858 for ten. Ring electrode from IEEE Std 142 Table 13. Grid from IEEE Std 80, the
simplified equation as modified by Sverak to include grid depth.
- Cross-checked two ways. The rod group was run against Sunde's independent closed
form for the same geometry: agreement within 8 % over several thousand combinations of
resistivity, rod length, diameter and spacing. The ring was run against the grid equation
with A = πa² and L_T = 2πa: the two published models sit within about 1 % at a 10 m ring
but spread to roughly 20 % at 40 m, because Sverak's grid equation carries no conductor
diameter at all while the ring equation does. Both are published; neither is "the" answer at
extreme geometries, and the page says so.
- Area floor. As L_T grows the 1/L_T term vanishes and R_g tends to
ρ ÷ √(20A) × (1 + 1/(1 + h√(20/A))). That floor is the resistance below which no amount of
extra conductor inside the footprint will go, and it is usually what decides whether a
substation earth is feasible on the land available.
- Uniform soil throughout. Layered ground, a water table, seasonal drying, frozen soil,
concrete-encased electrodes and chemical backfill are all outside the model.
- GPR = I_earth × R is Ohm's law and nothing more. It is shown because it is the figure that
drives insulation coordination, not because any safety assessment has been done.
Not covered: touch and step voltage, mesh voltage, surface-layer derating, fault
current division between the grid and other return paths, conductor thermal withstand, corrosion
life, and any statement of what resistance is permitted — that comes from the code and the
connection agreement.
City irradiance data
Built-in GHI values are approximate annual totals consistent with the ranges published by
the Global Solar Atlas
(World Bank / Solargis) and ESMAP. They are rounded and intended for option screening.
For any real project, pull site-specific data from
PVGIS
(free, hourly, Europe/Africa/Asia coverage) or purchase a Solargis or Vaisala prospecting report.
General limits of everything on this site
- All tools compute physics, not code compliance. Where a wiring code, grid code or product
standard governs — ampacity, overcurrent protection, earthing, anti-islanding — the tools
say so and stop.
- Constants are the open, published ones (IACS conductivities, IEC 60228 sizes, datasheet
temperature coefficients). No proprietary data is used or implied.
- Every calculator states its failure modes. If you find a result that contradicts its own
stated limits, that is a bug — report it.