Method & Sources

Every calculator here publishes what it assumes. This page collects the models, the constants, and — more importantly — where each one stops being accurate. If a number cannot be defended, it does not belong on this site.

Cable voltage drop

ρ(T) = ρ₂₀ × [1 + α × (T − 20)]
R = ρ(T) × L ÷ (A × n)
ΔV_dc = I × 2R   ΔV_1φ = I × 2R × cos φ   ΔV_3φ = √3 × I × R × cos φ

Not covered: ampacity (IEC 60364-5-52 / NEC Table 310.16 depend on installation method, grouping, ambient), short-circuit withstand, protective coordination.

Voltage rise from an exporting inverter

I_export = P ÷ (V × phases)
ΔV_rise = I_export × 2R (1φ)   ΔV_rise = √3 × I_export × R × cos φ (3φ)

Solar string configurator

V_oc(T) = V_oc,STC × [1 + α_voc × (T − 25)]
N_s,max = floor( V_dc,max × (1 − margin) ÷ V_oc(T_min) )
N_s,min = ceil( V_mppt,low ÷ V_mp(T_max) )

Battery bank sizer

C_eol = E_load × N ÷ (η_inv × √η_rte × DoD × f_T × SOH_EOL)

PV energy yield

GTI = GHI × TF(tilt, lat) × AF(azimuth)
PR = [1 + γ(T_cell − 25)] × η_inv × (1−s)(1−m)(1−dc)(1−ac) × A
E₁ = kWp × GTI × PR × (1 − clip)

Inverter sizing & DC/AC ratio

T_cell = T_amb + (NOCT − 20) ÷ 800 × G
k = (G ÷ 1000) × [1 + γ × (T_cell − 25)]
R_th = 1 ÷ (k × η_inv)   ← clipping begins above this DC/AC
loss_clear-sky day = (1 − x_th)^1.5,   x_th = R_th ÷ R_actual
loss_annual = f_clear × loss_clear-sky day

Not covered: DC input current and MPPT allocation (see the string configurator), conductor ampacity, overcurrent protection, DC isolator ratings, grid-code compliance.

Short-circuit current

The transformer impedance percentage is a per-unit figure, so it becomes ohms through the base impedance Z_base = V² ÷ S and is split into resistance and reactance with the X/R ratio. The cable adds its own resistance (from IACS conductivity, corrected to conductor temperature) and reactance (supplied by you, 0.08 Ω/km being a fair LV default). The two are added as complex numbers and the fault current follows from Ohm's law on the magnitude.

Isc = V_LL ÷ (√3 × |Z_tx + Z_cable|)
Isc,LN = (V_LL ÷ √3) ÷ |Z_tx + Z_phase + Z_neutral|

Not covered: protective device selection, breaking capacity, discrimination, disconnection time, and the k factor for thermal withstand — those belong to the applicable code. The adiabatic minimum shown on the page is informational only.

Solar row spacing

Sun position comes from the standard low-precision solar equations: declination from the day of year, hour angle from solar time, then altitude and azimuth from spherical trigonometry. The declination expression δ = −23.44°·cos(360/365·(N+10)) is accurate to roughly half a degree across the year, which is far tighter than the shadow geometry needs.

sin α = sin φ · sin δ + cos φ · cos δ · cos h
D = H · cos(A − A_array) ÷ tan α
GCR = w · sin(tilt) ÷ (w · cos(tilt) + D)

Not covered: single-axis trackers (their obstruction height and effective width change continuously, and backtracking changes the optimum again), terrain or building horizons, and any setback or fire-access requirement from local code — those usually dominate row pitch anyway.

Earthing and grounding resistance

R₁ = ρ ÷ (2πL) × [ ln(8L/d) − 1 ]
Rₙ = (R₁ ÷ n) × (1 + λα),  α = ρ ÷ (2πsR₁),  λ = 2H(n−1) − 2(n−1)/n
R_ring = ρ ÷ (2π²a) × [ ln(8a/r) + ln(1 + h/2a) − 1.116 ]
R_g = ρ × [ 1/L_T + 1/√(20A) × (1 + 1/(1 + h√(20/A))) ]

Not covered: touch and step voltage, mesh voltage, surface-layer derating, fault current division between the grid and other return paths, conductor thermal withstand, corrosion life, and any statement of what resistance is permitted — that comes from the code and the connection agreement.

City irradiance data

Built-in GHI values are approximate annual totals consistent with the ranges published by the Global Solar Atlas (World Bank / Solargis) and ESMAP. They are rounded and intended for option screening. For any real project, pull site-specific data from PVGIS (free, hourly, Europe/Africa/Asia coverage) or purchase a Solargis or Vaisala prospecting report.

General limits of everything on this site