Size a conductor so the load actually gets the voltage it needs. Handles DC, single-phase and three-phase circuits, copper or aluminium, with temperature correction and parallel runs. The same numbers read as voltage rise when the current flows the other way — see voltage rise at a solar point of connection, or use the dedicated voltage rise calculator which models the baseline voltage and the inverter trip threshold explicitly. Runs entirely in your browser — nothing is uploaded.
Circuit
Use the hot-running value, not ambient.
1.0 gives the most conservative drop.
Result
| Size | R one way | Drop | Drop | Limit |
|---|
Sizes shown are a window around your selection, not a full catalogue.
Quick answer. On a 230 V single-phase circuit, keep voltage drop under 3 % (6.9 V) for lighting and 5 % (11.5 V) for other loads; on a 400 V three-phase circuit the same limits are 12 V and 20 V. Solar DC arrays and battery leads are normally designed to 1–2 %, because every volt lost is energy never delivered. Drop is ΔV = 2 × I × R for DC and single-phase and √3 × I × R × cos φ for three-phase, with R taken at the conductor's hot-running temperature — about 20 % higher at 70 °C than the 20 °C tables quote.
It answers one question: given this current, this distance and this conductor, how much voltage is lost on the way, and is that acceptable. It also works backwards — tell it the drop you can live with and it returns the smallest standard size that gets you there.
Where ρ₂₀ is 17.241 Ω·mm²/km for copper and 28.264 Ω·mm²/km for aluminium, α is 0.00393 /°C for copper and 0.00403 /°C for aluminium, L is one-way length, A is conductor area and n is the number of parallel runs per phase.
Reference tables are quoted at 20 °C. A cable sized from those tables and then run at 70 °C has about 20 % more resistance than the table implies, so the drop is about 20 % worse than the cold calculation. On long runs that is the difference between passing and failing. Set the temperature field to the conductor's expected hot-running value, not the ambient.
A 1000 V DC solar string: 13 A, 120 m of 4 mm² copper, conductor at 60 °C.
1.56 % passes a 3 % limit comfortably, but 202 W is not free — across a year of full-load operation that is about 1 770 kWh of energy turned into heat in the cable. Real arrays spend most of the day below peak, so treat that figure as an upper bound, but it is exactly why solar DC sides are usually designed to 1–2 % rather than the 3 % used for building wiring.
Both IEC 60364-5-52 and the NEC informational note to 210.19(A) present 3 %/5 % as recommendations rather than mandatory limits, so the figure is a design choice. Underground distribution and utility work often uses different figures again.
A grid-tied inverter pushes current back up the same cable. The resistance that causes voltage drop when you draw power causes voltage rise when you export it. The arithmetic is identical — only the sign changes.
Using this page as a voltage rise calculator: put the inverter's export current in the load current field, put the distance from the inverter back to the transformer in the length field, and read the drop result as the rise. Same number, opposite direction. If you would rather enter the inverter's kW rating and see how much headroom is left before the over-voltage trip, the voltage rise calculator does that directly.
Two things stack up against you. First, the rise is proportional to the impedance between the transformer and your point of connection, so a long rural run is punished twice — once by distance, once by the size you thought was fine for ampacity. Second, the grid's own voltage is at its daily highest at exactly the moment your export peaks, because every other system on the feeder is exporting too. The rise does not start from nominal; it starts from whatever the feeder is already sitting at.
When the sum crosses the inverter's over-voltage trip threshold — commonly around 110 % of nominal, so roughly 253 V on a 230 V system, though the exact figure is set by the regional interconnection rule — the inverter disconnects, waits, and reconnects. On site that presents as the system dropping out repeatedly around solar noon and being fine in the morning, which is precisely when the energy is worth the most. Owners usually blame the inverter. It is almost always the cable.
A 5 kW single-phase inverter on a 230 V system, 40 m of 6 mm² copper back to the transformer, conductor at 60 °C.
6 mm² carries 21.7 A without breaking a sweat — ampacity is not the constraint. The rise is. Jumping to 16 mm² roughly halves the resistance per metre and brings the rise under 1 %, which is the sort of figure connection agreements typically ask for at the point of common coupling. This is why solar AC runs so often look two or three sizes oversized to anyone sizing them by current alone.
One thing worth checking before you spend money: on a long feeder the worst case may not be one direction. Midday can show rise at the far end while the evening peak shows drop. Size for whichever is worse, and note that the same cable is being asked to do both.