Cable Voltage Drop Calculator

Size a conductor so the load actually gets the voltage it needs. Handles DC, single-phase and three-phase circuits, copper or aluminium, with temperature correction and parallel runs. The same numbers read as voltage rise when the current flows the other way — see voltage rise at a solar point of connection, or use the dedicated voltage rise calculator which models the baseline voltage and the inverter trip threshold explicitly. Runs entirely in your browser — nothing is uploaded.

Circuit

Use the hot-running value, not ambient.

1.0 gives the most conservative drop.

Result

Voltage drop
– V
Drop
– %
Voltage at load
– V
Loss in cable
– W
Enter your circuit values.

Size R one way Drop Drop Limit

Sizes shown are a window around your selection, not a full catalogue.

Quick answer. On a 230 V single-phase circuit, keep voltage drop under 3 % (6.9 V) for lighting and 5 % (11.5 V) for other loads; on a 400 V three-phase circuit the same limits are 12 V and 20 V. Solar DC arrays and battery leads are normally designed to 1–2 %, because every volt lost is energy never delivered. Drop is ΔV = 2 × I × R for DC and single-phase and √3 × I × R × cos φ for three-phase, with R taken at the conductor's hot-running temperature — about 20 % higher at 70 °C than the 20 °C tables quote.

What this calculator does

It answers one question: given this current, this distance and this conductor, how much voltage is lost on the way, and is that acceptable. It also works backwards — tell it the drop you can live with and it returns the smallest standard size that gets you there.

The calculation

ρ(T) = ρ₂₀ × [1 + α × (T − 20)]
R = ρ(T) × L ÷ (A × n)
ΔV = I × 2R (DC and single-phase)
ΔV = √3 × I × R × cos φ (three-phase, line-to-line)
P_loss = I² × 2R or 3 × I² × R

Where ρ₂₀ is 17.241 Ω·mm²/km for copper and 28.264 Ω·mm²/km for aluminium, α is 0.00393 /°C for copper and 0.00403 /°C for aluminium, L is one-way length, A is conductor area and n is the number of parallel runs per phase.

Temperature is the part people skip

Reference tables are quoted at 20 °C. A cable sized from those tables and then run at 70 °C has about 20 % more resistance than the table implies, so the drop is about 20 % worse than the cold calculation. On long runs that is the difference between passing and failing. Set the temperature field to the conductor's expected hot-running value, not the ambient.

Worked example

A 1000 V DC solar string: 13 A, 120 m of 4 mm² copper, conductor at 60 °C.

ρ(60) = 17.241 × [1 + 0.00393 × 40] = 19.95 Ω·mm²/km
R = 19.95 × 0.120 ÷ 4 = 0.599 Ω
ΔV = 13 × 2 × 0.599 = 15.6 V → 1.56 %
P_loss = 13² × 2 × 0.599 = 202 W

1.56 % passes a 3 % limit comfortably, but 202 W is not free — across a year of full-load operation that is about 1 770 kWh of energy turned into heat in the cable. Real arrays spend most of the day below peak, so treat that figure as an upper bound, but it is exactly why solar DC sides are usually designed to 1–2 % rather than the 3 % used for building wiring.

What this tool does not do. It calculates voltage drop only. It does not check current-carrying capacity, short-circuit withstand, or protective-device coordination — those depend on installation method, grouping, ambient conditions and the wiring code in force where you are. Confirm ampacity against your local code before ordering cable.

Which drop limit should you use?

Both IEC 60364-5-52 and the NEC informational note to 210.19(A) present 3 %/5 % as recommendations rather than mandatory limits, so the figure is a design choice. Underground distribution and utility work often uses different figures again.

Voltage rise: the same calculation in reverse

A grid-tied inverter pushes current back up the same cable. The resistance that causes voltage drop when you draw power causes voltage rise when you export it. The arithmetic is identical — only the sign changes.

I_export ≈ P_inverter ÷ (V × number of phases)
ΔV_rise = I_export × 2R (single-phase)
ΔV_rise = √3 × I_export × R × cos φ (three-phase, line-to-line)

Using this page as a voltage rise calculator: put the inverter's export current in the load current field, put the distance from the inverter back to the transformer in the length field, and read the drop result as the rise. Same number, opposite direction. If you would rather enter the inverter's kW rating and see how much headroom is left before the over-voltage trip, the voltage rise calculator does that directly.

Why it bites

Two things stack up against you. First, the rise is proportional to the impedance between the transformer and your point of connection, so a long rural run is punished twice — once by distance, once by the size you thought was fine for ampacity. Second, the grid's own voltage is at its daily highest at exactly the moment your export peaks, because every other system on the feeder is exporting too. The rise does not start from nominal; it starts from whatever the feeder is already sitting at.

When the sum crosses the inverter's over-voltage trip threshold — commonly around 110 % of nominal, so roughly 253 V on a 230 V system, though the exact figure is set by the regional interconnection rule — the inverter disconnects, waits, and reconnects. On site that presents as the system dropping out repeatedly around solar noon and being fine in the morning, which is precisely when the energy is worth the most. Owners usually blame the inverter. It is almost always the cable.

Worked example: rise on a solar AC run

A 5 kW single-phase inverter on a 230 V system, 40 m of 6 mm² copper back to the transformer, conductor at 60 °C.

I_export = 5000 ÷ 230 = 21.7 A
ρ(60) = 17.241 × [1 + 0.00393 × 40] = 19.95 Ω·mm²/km
R = 19.95 × 0.040 ÷ 6 = 0.133 Ω
ΔV_rise = 21.7 × 2 × 0.133 = 5.8 V → 2.5 % of 230 V
At 16 mm²: R = 0.0499 Ω, ΔV_rise = 2.2 V → 0.94 %

6 mm² carries 21.7 A without breaking a sweat — ampacity is not the constraint. The rise is. Jumping to 16 mm² roughly halves the resistance per metre and brings the rise under 1 %, which is the sort of figure connection agreements typically ask for at the point of common coupling. This is why solar AC runs so often look two or three sizes oversized to anyone sizing them by current alone.

The limit is a contract, not a constant. Caps of around 1–2 % at the point of connection are common, and some networks allow more where the pre-connection voltage is measured low, but the number that governs your job is the one written in your connection agreement. Confirm it with your utility or DNO before you size cable against it. This tool gives you the physics; it does not know your contract.

If the rise is already too high

One thing worth checking before you spend money: on a long feeder the worst case may not be one direction. Midday can show rise at the far end while the evening peak shows drop. Size for whichever is worse, and note that the same cable is being asked to do both.

Frequently asked

What voltage drop is acceptable?
Common practice is 3 % for lighting and 5 % for other loads, measured to the farthest outlet. Solar DC arrays are usually designed to 1–2 %, because every volt lost is energy never delivered.
Why does conductor temperature change the result?
Copper resistivity rises about 0.393 % per °C, aluminium about 0.403 %. Calculated at 20 °C but running at 70 °C, a conductor has roughly 20 % higher resistance, so the real drop is about 20 % worse than the cold figure.
Does this check current-carrying capacity?
No. This tool computes voltage drop only. Ampacity depends on installation method, grouping, ambient temperature and your local wiring code, and must be verified separately.
Is the three-phase result line-to-line or line-to-neutral?
Line-to-line. The √3 factor is applied to the resistance of one conductor, giving the drop in line-to-line voltage under balanced load.
Can I use this as a voltage rise calculator for solar?
Yes. Rise from an exporting inverter is drop with the current reversed — same formula, opposite sign. Put the inverter's export current in the current field and the run back to the transformer in the length field, then read the result as the rise. Connection agreements commonly cap the rise at the point of connection at around 1–2 %, so solar AC runs are often sized well above what ampacity alone needs. Confirm the actual limit with your utility or DNO.
Can I use it for aluminium?
Yes — select aluminium and the resistivity and temperature coefficient switch accordingly. Expect roughly 1.6× the drop of an equivalent copper conductor.

Related calculators